12V 7ah Backup Battery (20hr battery)

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Guangdong

  • Validity to:

    Long-term effective

  • Last update:

    2017-09-28 03:11

  • Browse the number:

    252

Send an inquiries

Company Profile

Henan Hengming Fengyun Power Source Co., Ltd.

By certification [File Integrity]

Contact:Ms. Jenny Wei(Mr.)  

Email:

Telephone:

Area:Guangdong

Address:Guangdong

Website: http://gzxuntian.auto-huaxin.com/

Product details
We produce VRLA/SLA Battery, lead battery, Industrial Battery, 12V/ 6V Battery, Rechargeable Battery, Gel Battery, Deep Cycle Battery, sealed lead acid battery and so on.

12v 7ah backup battery (20hr battery)

Valve regulated lead acid series UPS batteries are designed with AGM (Absorbent Glass Mat) technology, high performance plates and electrolyte to gain extra power output for common power backup system applications widely used in the field of UPS, Emergency Lighting System.

Battery Structure
1. Container/Cover: Made of UL94HB and LU 94V-0 ABS Plastic
2. Negative Plates: Use the special PbCa alloy grids, optimize the recombination efficiency and less gassing.
3. Separator: Import high quality AGM separator.
4. Postive Plates: PbCa grids minimize corrosion and prolong life.
5. Terminal post: Cooper material with maximum conductivity, enhance the high current rapidly.
6. Vent Valve: Allows the release of excess gas automatically for safety.

Application
UPS, solar systems, control systems, power systems, wind energy systems, telecommunication/communication systems & etc.

Characteristics
1. Excellent safety performance.
2. Good dischargeing performance.
3. Good stock-proof performance.
4. Good impact-proof performance.
5. Good resistance to overdischarge.
6. Good resistance to overcharge.
7. Good resistance to high current.

Operation and maintenance manual
For maintenance free battery, it's free maintenance in the operation. But we can only use it in proper operation to keep the long lifetime of the battery,

(1) Battery Installation
Batteries should be installed possibly in a clean, cool, ventilated and dry place. The battery should be placed upright. Each terminal between the batteries is connected firmly.
(2) The ambient temperature
Ambient temperature is important factor for the battery operation. When the ambient temperature is too high, Battery plate corrosion will be increased, while absorbing more moisture; When the ambient temperature is too low, the battery will not be full charged. All this will affect the battery life. Therefore we suggest the working ambient temperature is around 25 º C.
(3) The charge and discharge current
Battery charge and discharge current usually uses the concept C, the actual value of C is related to the capacity of the battery. For example, a 100AH battery: 1C = 100A. Charging current is around 0.1C; The charging current must not be bigger than 0.3C. Discharge current general requirements in 0.05 ~ 3C range.
(4) Charging voltage
After the battery is full converted to float charging, the float voltage is around 13.0V. If the charging voltage is too high will cause the battery overcharge, otherwise the battery will not be full charged. Charging voltage is abnormal, it may be caused by the battery configuration error, or it may be caused by controller failure. Do not choose the controller with bad quality.
(5) The depth of discharge
Depth of discharge of the battery life is also a important factor for lifetime of battery, the deeper the battery discharge, the fewer the number of cycles, so battery should avoided from deep discharge.
(6) Regular maintenance
Battery should be regular checked in every period time after used, such as check its outlook, measuring the average voltage of each battery, etc.

Data Sheet
Capacity 77° F(25º C) 20 hours rate(0.35A 10.5V) 7.0Ah
10 hours rate(0.66A 10.5V) 6.6Ah
5 hours rate(1.2A 10.5V) 6.0Ah
1 hour rate(4.3A 9.6V) 4.3Ah
Internal Resistance Full charged battery 77° F(25º C): 22mΩ
Capacity affected by Temperature (20 hour rate) 104° F(40º C) 102%
77° F(25º C) 100%
32° F(10º C) 85%
5° F(-15º C) 65%
Self-Discharge 68° F(20º C) Capacity after 3 month storage 90%
Capacity after 6 month storage 80%
Capacity after 12 month storage 60%
Max discharge current77° F(25º C): 105A(5S)
Charge (Constant Voltage) Float: 13.6 to 13.8V/77° F/(25º C)
Cycle: 14.5 to 14.9V/77° F/(25º C)
Max Current: 1.75A